Standard Rating : 0.8-10 AMPERE
Input Power : 125 VAC / 250 VAC / 12 VDC /24 VDC
Dielectric Strength : 1500VAC / 1 Minute.
Interrupt Capacity : 125 VAC x 1000A
Insulation Resistance
:>100 M?G[
Calibration :
25°C-100% of Rated Current-Continuously Carried.
25°C-Between 101% to 149%-May Trip or Not.
25°C-150% of Rated Current-Trip Within 1 HR.
25°C-200% of Rated Current-Trip Within 2-50 Sec
25°C-300% of Rated Current-Trip Within 0.5-5 Sec
25°C-400% of Rated Current-Trip Within 0.3-1 Sec
25°C-500% of Rated Current-Trip Within 0.2-0.7 Sec 25°C-600% of Rated Current-Trip Within 0.1-0.5 Sec
Contact Endurance : 125 VAC x 200% of Rated Current -500 Cycles.
Reset Method:Auto Reset.
Maximum Internal Resistance
|